EU Data Center Water Grades Miss Up to 86% of the Footprint
EU Data Center Water Grades Miss Up to 86% of the Footprint Brussels’ new A-to-G label measures water at the site meter. The power plants feeding the grid use far more. The EU's new water label only measures a fraction of a data center's total water use. It le
Illustrative imageEU Data Center Water Grades Miss Up to 86% of the Footprint
Brussels’ new A-to-G label measures water at the site meter. The power plants feeding the grid use far more.
The EU's new water label only measures a fraction of a data center's total water use. It leaves out the water that power plants use to generate electricity. Depending on how you measure it, the label misses anywhere from 57% to 86% of the total water footprint.
The European Commission adopted a new rule on September 21, 2026, that will assign a water efficiency grade to data centers. This rule will take effect if the European Parliament and Council raise no objections during their review period. Reporting is mandatory for all facilities with at least 500 kW of installed IT power. Starting August 15, 2027, the database will issue official A-to-G labels based on a facility's Water Usage Effectiveness (WUE), measured in liters per kilowatt-hour of IT load. Top-performing sites with a WUE at or below 0.1 will receive an A grade, while sites scoring above 1.0 will receive a G.
Current metrics
When The Green Grid created the Water Usage Effectiveness (WUE) metric in 2011, they offered two versions. The standard version only counts water used on-site, like the water that evaporates during cooling or controls humidity. The second version, called "Source WUE," looks at the bigger picture. It adds the water that power plants use to make the electricity running the building, which is calculated by multiplying the grid’s water use per kilowatt-hour by the site’s energy efficiency score (PUE) and adding it to the on-site water.
To explain why Source WUE matters, the authors shared a specific scenario: a data center that switches to a cooling system that uses more electricity instead of direct water. While the building looks more efficient on paper, it forces power plants to consume more water. The authors noted that in these cases, "the water use may simply be shifted from one site to another, while the ecosystem’s total water use may actually go up."
In a December 2024 report to Congress, the Lawrence Berkeley National Laboratory provided concrete numbers for the U.S. data center footprint. In 2023, these facilities used 66 billion liters of water on-site for direct cooling. However, the 176 terawatt-hours of electricity they pulled from the grid forced power plants to consume an additional 800 billion liters of water, averaging 4.52 liters per kilowatt-hour. In sum, the hidden water cost at the power plant is roughly 12 times larger than the water used on-site.
Berkeley Lab includes the water that evaporates from hydroelectric reservoirs, while The Green Grid sets hydropower water use to zero. Our European calculation follows The Green Grid and leaves hydropower out of the main result.
EU measurements
Under EU Delegated Regulation 2024/1364, any data center with at least 500 kW of installed IT power must report its total on-site water intake to the European database.
The European Commission's first technical report on this data states that "indirect water consumption (e.g. by power plants for electricity generation) is not considered." This is because the law only requires data centers to report water usage categories 1 and 2 under the EN 50600-4-9 standard.
The first reporting round collected data from 770 data centers. This represents about 36% of the facilities required to report. Out of those, 458 data centers reported using water. The Commission’s consultants rated the WUE values from 43 of the reporting data centers as potentially unreliable, “often reported as N/A or exceeding realistic limits.”
- Water-to-Energy Efficiency: The average energy-weighted WUE score was 0.58. Finland was the most efficient at 0.07, while Belgium was the least efficient at 1.28.
- Total use: Across all participating sites, data centers reported using a total of 6.2 million cubic meters of water, while consuming 14,088 GWh of total energy.
Off-site water use
To calculate a country's total water score (WUEsource) exactly as the 2011 paper defined it, we use a three-step process.
1. Find the power mix: Look at each country's 2023 electricity mix using Ember’s yearly electricity dataset to see its share of coal, gas, nuclear, and renewables.
2. Apply the water factors: Use The Green Grid’s intensity factors to calculate the grid's total water use per kilowatt-hour (kWh):
- Nuclear: 3.3 liters per kWh
- Coal: 2.2 liters per kWh
- Oil & unknown fossil fuels: 1.8 liters per kWh
- Gas: 0.8 liters per kWh
- Wind, Solar, & Hydro: 0 liters per kWh
- Note: For biomass steam and freshwater flash geothermal plants, use the cooling tower medians from the National Renewable Energy Laboratory's (NREL) 2011 review.
3. Do the math: Multiply that final grid water figure by the country's reported PUE, then add it to the reported WUE.
Figure 1. Reported site WUE and site plus grid WUE for 15 member states, liters per kWh of IT load. Dashed line marks the label's G threshold of 1.0. Sources: EU first technical report, Ember, Green Grid WP#35, NREL.
The total EU-27 power grid averages 1.33 liters of water per kWh. This means the grid alone surpasses the EU’s water label "G band" threshold (1.0) before a data center even turns on its own cooling systems. In fact, 13 out of 27 national power grids break this threshold entirely on their own.
When we look at the 15 countries with usable data, the total water footprint (site plus grid) averages 2.29 liters per kWh. The water used directly on-site makes up just 24% of that total amount. The remaining 76% is the hidden water used by power plants. The EU counts water withdrawn (taken in) at the site, while the standard factors count water consumed (evaporated or otherwise not returned) at the power plant. If we measured both the exact same way, the on-site share would drop even lower than 24%, because power plants take in massive amounts of water that they eventually return to the source.
Because these standard factors are based on U.S. power plants, we re-tested the math using alternative data models, including the National Renewable Energy Laboratory (NREL) metrics and the Berkeley Lab models (which include reservoir evaporation). Across every single model tested, the water used at the power plants is 1.3 to 6.0 times higher than the water recorded at the data center's meter. We use The Green Grid factors as the central estimate, since they come from the paper that defined WUE source.
Figure 2. Data center water use (site WUE) compared to power grid water intensity across 15 EU member states. As The Green Grid predicted, data centers located in countries with higher grid water intensity tend to report lower on-site water use, though the sample size is limited to 15 countries. Sources: EU first technical report, Ember, Green Grid WP#35, NREL.
Label
Looking ahead, the European Commission has stated that this new water label will be used to evaluate facilities under the proposed Cloud and AI Development Act. Meanwhile, broader global standards remain vague. Just five days before the EU adopted its rules, every G20 member at the Houston energy ministerial agreed to a voluntary water reuse agreement. While this global document explicitly names data centers as a key sector for future case studies, it fails to include any specific standard for how to actually measure that water use.
Because the European database already pulls a data center's location to automatically fill in regional weather data, it could easily calculate grid water the exact same way. The database could automatically pull the country's electricity mix, multiply it by the facility's reported PUE score, and display the result as a separate number next to the official grade. This requires absolutely no new paperwork from data center operators. It also keeps the grading system fair: a highly efficient facility located on a water-heavy grid, like France's nuclear network, retains the strong grade it earned at its own meter, while buyers still see the total water footprint. Furthermore, while the EU currently pairs labels with local water stress data, grid electricity is often generated by power plants in entirely different regions or countries. Displaying the grid water footprint captures this hidden impact.
If you are a sustainability or EHS manager purchasing data center space in the EU, you can take action right now:
- Calculate the full footprint: Ask your providers for their current on-site water (WUE) and energy efficiency (PUE) scores. Then, use the intensity factors listed above to calculate and add the grid water footprint based on that country's electricity mix.
- Compare accurately: Always use the combined figure (site plus grid) when comparing facilities in different countries.
- Report honestly: Do not cite an official "A" grade by itself as proof of low water use in your own corporate sustainability reports, since that grade completely misses the grid's hidden water impact.
Seyfi Gasilov leads Gasilov Group’s sustainability reporting and AI governance practice. He holds LL.M. degrees in international and European law and spent 15 years in New York and Canada running and restructuring growing businesses.